Technical details for INSTA- POWERTM make ON line UPS, Cap. 1 to 500 KVA with Standard
SMF Batteries for 30 Minutes battery back-up
Make & Type
INSTA-POWERTM make ON line UPS pure sine wave PWM technology
with Standard SMF Batteries for 30 Minutes battery back-up
Capacity
1 KVA to 500 KVA
Battery
DC-Voltage
36V to 360V
Input
230 V+15%-20%
415 V +10%
Output
230 volts + 1%
230 volts + 1%/415 V +1%
Nos. of Phases
1 Phase/1 Phase
3 Phase/1Phase
3 Phase/3 Phase
Frequency I/P
50Hz ± 6%
50Hz ± 6%
Frequency O/P
50Hz ± 1%
50Hz ± 1%
Type of Operating
Auto & Manually
Auto & Manually
Type of Operating
10 msec
10 msec
Efficiency
> 93%
> 93%
Effect of power factor
Nil
Nil
Charging Time
12 Hours for 90% of full Capacity
Charger Type
Internal Controlled Rectifier type
Technology
IGBT / MOSFET High Frequency PWM
Voltage Regulation
± 1% for DC I/P Variation & O/P Load Variation
Waveform
PWM Sine wave
Harmonic Distortion
Less than 3%
Power Factor
0.8
Overload
125% for 5 minutes
150% for 60 sec
Crest Factor
3:1
Transient Response
± 4% under full load change and corrected within 60msec
Audible Noise
Less than 45 dB at 1 Meter
Metering
Microprocessor based Digital LCD Metering for Input-Output
Voltage, Output Frequency, Load Percentage, Battery
Voltage, Battery current, Battery percentage.
Operating
Temperature
00C to 500C
Humidity
Max 95%, No condensing
PROTECTIONS
Overload
System trips with indication
Output Short-circuit
System trips
Output over/ Under
Voltage
System trips with fault indication
Dc Over voltage
System trips with fault indication
Battery Low
Pre-Alarm and Switch Off
I
NDICATIONS & ALARMS
Mains on
Indication
Inverter on
ndication
Battery Low
Indication & Alarm
Fault Conditions
Indication & Alarm
Mains Fail
Indication & Alarm
Output Overload
Indication & Alarm
Battery Level
% Battery on LCD Display
Load Level
% Load on LCD Display
CHANGEOVER
Electro- mechanical
Switch
Provided as Standard feature
ISOLATION OF POWER
Input
MCB Provided
Battery
HRC Fuse
COMPUTER INTERFACE
Interface type
DB-9 (Dry contact type)
Software Compatibility
(software Optional
For Windows 95 /98, Windows 2000, Windows XP.
BATTERY BANK
Type of Battery
Standard SMF Battery
Accessories
i) Set of inter row & inter bank Connectors with battery
ii) Battery mounting Rack (optional)
* Specifications are subject to change without prior notice due to constant Improvement in design & technology.